2.04 Fire Sprinkler SubmittalReference: 2007 C.B.C. Section 111.3, NFPA 13, 2002 edition, Chapter 14
This bulletin describes the information to be provided when plans are submitted for a building permit to install or modify a fire sprinkler system. Legible and readable working plans shall be drawn to an indicated scale (not smaller than 1/8 inch = 1 foot), on sheets of uniform size (11 inches by 17 inches minimum), with a plan of each floor. The scope of work must be indicated and the standards used must be referenced, including the edition (e.g., NFPA 13, 13D, 13R). Plans shall show those items from the following list which pertain to the design of the system. All details and information on drawing must be of sufficient size and clarity to be legible and microfilmed. Plans must not be submitted on a reflected ceiling plan.
Please note that only the drawings are microfilmed and that all pertinent information regarding the sprinkler system shall be on the drawings. Therefore any references to submittal specification sheets or hydraulic calculations are not acceptable.
1. Name and phone number of owner and occupant;
2. Address of building, including lot and block number;
3. Name, address, phone, and fax number of contractor;
4. Two sets of plans and one set of hydraulic calculations with the wet signature and stamp of the engineer or design-build C-16 contractor, include the processed SFFD water-flow request form (see item 15). Provide one set of manufacturer's specification sheets for all components of the system;
5. Full height cross section, or schematic diagram, if required for clarity; including ceiling construction including height, type (beam, smooth), including open to the floor above, skylights. etc.; and method of protection for nonmetallic piping. Show beam size, material, and location on plan.
6. Provide a detailed and labeled riser/standpipe detail;
7. Provide site map of building location with directional indicator (this is required on all sheets);
8. Show all street locations and indicate main entrance to building for Fire Department access;
9. Indicate any windows that require exposure protection and for what reason and provide detail showing mullions, sprinkler orientation, dimensions etc.
10. Storage occupancies must show commodities being stored, maximum storage height, and distance from the ceiling or top of storage to sprinkler deflector: Please note: The drawings must include a completed Owners Information Certificate , Fig. A.14.1(b) NFPA 13-2002.
11. If modifications are being done to a hydraulically designed sprinkler system, and the work being done is in a hydraulically remote area, provide hydraulic calculations;
12. Locations of fire walls and partitions, and occupancy class and use of each area or room;
13. Location and size of concealed spaces, indicating if they are combustible or non-combustible construction, closets, attics, and bathrooms;
14. Identify any small enclosures or spaces in which no sprinklers are to be installed and explain why and provide code sections;
15. Size of city main in street and whether it is dead-end or circulating; and, if dead-end, direction and distance to the nearest circulating main; Provide a copy of the processed SFFD Waterflow Request form with City main test results. Provide system elevation relative to test hydrant;
16. Other sources of water supply, with pressure or elevation;
17. Underground pipe size, length, location, weight, material (complete description i.e. cement lined ductile iron), and point of connection to city main; the type of valves, meters, and valve pits; and the depth that the top of the pipe is laid below grade;
18. Piping provisions for flushing;
19. Approximate capacity in gallons of dry pipe system;
20. Pipe type and schedule of wall thickness;
21. Nominal pipe size and cutting lengths of pipe using center to center dimensions; Note: Where typical branch lines prevail, it will be necessary to size only one typical line.
22. Location, size and length of riser nipple or drop;
23. Type of fittings(including description i.e. 125# cast iron threaded fittings, mechanical joints, above/belowground) and joints and location of all welds and bends. The contractor shall specify on the drawing any sections to be shop welded (non-restraint type joint) and the type of fittings or formations to be used. For mechanical joints on underground piping provide thrust block size and details.
24. All control valves, check valves, drain pipes, and test connections including inspectors test assembly, also show 1/4" relief valve for grid systems;
25. Make, type, model, and size of alarm or dry pipe valve;
26. Make, type, model, and size of preaction or deluge valve;
27. Kind and location of alarm bells;
28. Size and location of hose outlets, hand hose, and related equipment;
29. The setting for pressure-reducing valves, include both static and residual pressures;
30. Information about backflow preventers (manufacturer, size, type);
31. SIN (Sprinkler Identification Number), manufacturer, manufacturer's model number, response type, temperature rating, sprinkler type, orifice size, and any other necessary identification information for all sprinklers used;
32. Temperature rating and location of high-temperature sprinklers;
33. Manufacturer's installation instructions and technical data for any specially listed equipment, including descriptions, applications, and limitations for any sprinklers, devices, piping, or fittings. This includes backflow preventers, fire pumps (including pump curves), and pressure reducing valves, special design systems and accessory devices.
34. Total area protected by each system on each floor;
35. Number of sprinklers on each riser per floor;
36. Total number of sprinklers on each dry pipe system, pre-action system, combined dry pipe-pre-action system, or deluge system;
37. Hydraulic calculations or pipe schedule design criteria;
38. For hydraulically designed systems, the information on the hydraulic data nameplate for the most remote area for each hazard;
39. Hydraulic reference points shown on the plan shall correspond with comparable reference points on the hydraulic calculation sheets. Outline/highlight remote area;
40. Provide on the plan the minimum rate of water application (density), the design area of water application, in-rack sprinkler demand, and the water required for hose streams both inside and outside.
41. Provide on the plan the total quantity of water and the pressure required noted at a common reference point for each system;
42. Relative elevations of sprinklers, distance of sprinkler deflector to ceiling, junction points, and supply or reference points;
43. If room design method is used, all unprotected wall openings throughout the protected floor;
44. Seismic sway bracing and hangers, sleeves, braces; methods of securing sprinklers: Provide type, manufacturer, size, and figure # for hanger components, including maximum size pipe hanger can support; fastener type, manufacturer, size,length minimum embedment depth, ceiling/beam/joist information (type, material, size) fastener is attached to;
45. Provide end-of-line restraint for end sprinkler on each branchline.
46. Calculation of loads for sway bracing, include details. See SFFD Administrative Bulletin 4.22
47. Any modification to an existing sprinkler system shall require seismic upgrades to all exposed and accessible portions within the area of work. These upgrades will be to the current NFPA 13 and the 2007 CBC standards. See SFFD Administrative Bulletin 4.22.
48. Where the equipment is to be installed as an addition to an existing system, enough of the existing system shall be indicated on the plans to make all conditions clear.
49. Any modification to an existing system shall include removal of unused excess piping. Relocation of heads shall be according to approved plan. Field installations which do not reflect the approved set of plans shall require recalculation of the system, taking into account all new piping and fittings.